15. USING A DIRECT DRIVE MOTOR
15 - 18
15.4.2 Power supply capacity and generated loss
Table 15.1 indicates servo amplifiers' power supply capacities and losses generated under rated load. For
thermal design of an enclosed type cabinet, use the values in the table in consideration for the worst
operating conditions. The actual amount of generated heat will be intermediate between values at rated
torque and servo-off according to the duty used during operation. When the servo motor is run at less than
the rated speed, the power supply capacity will be smaller than the value in the table, but the servo
amplifier's generated heat will not change.
Table 15.1 Power supply capacity and generated loss per direct drive motor at rated output
Servo amplifier-generated heat [W]
Servo motor
Power supply
capacity [kVA]
At rated output With servo-off
Area required for heat
dissipation [m
2
]
TM-RFM002C20 0.25 25 15 0.5
TM-RFM004C20 0.38 35 15 0.7
TM-RFM006C20 0.53 40 15 0.8
TM-RFM006E20 0.46 40 15 0.8
TM-RFM012E20 0.81 50 15 1.0
TM-RFM018E20 1.3 50 15 1.0
TM-RFM012G20 0.71 50 15 1.0
TM-RFM048G20 2.7 90 20 1.8
TM-RFM072G20 3.8 110 20 2.2
TM-RFM040J10 1.2 50 15 1.0
TM-RFM120J10 3.4 90 20 1.8
TM-RFM240J10 6.6 160 25 3.2
15.4.3 Dynamic brake characteristics
POINT
Do not use dynamic brake to stop in a normal operation as it is the function to
stop in emergency.
For a machine operating at the recommended load to motor inertia ratio or less,
the estimated number of usage times of the dynamic brake is 1000 times while
the machine decelerates from the rated speed to a stop once in 10 minutes.
Be sure to enable EM1 (Forced stop 1) after the direct drive motor stops when
using EM1 (Forced stop 1) frequently in other than emergency.