11. Options and peripheral devices
11 - 29
(5) Other precautions
(a) Always use the dedicated stand-alone reactor (FR-CVL) as the power factor improving reactor. Do
not use the power factor improving AC reactor (FR-HAL) or Power factor improving DC reactor (FR-
HEL).
(b) The inputs/outputs (main circuits) of the FR-CV and servo amplifiers include high-frequency
components and may provide electromagnetic wave interference to communication equipment (such
as AM radios) used near them. In this case, interference can be reduced by installing the radio noise
filter (FR-BIF) or line noise filter (FR-BSF01, FR-BLF).
(c) The overall wiring length for connection of the DC power supply between the FR-CV and servo
amplifiers should be 5 m or less, and the wiring must be twisted.
(6) Specifications
Power regenerative common
converter FR-CV-_
Item
7.5K 11K 15K 22K 30K 37K 55K
Total of connectable servo amplifier
capacities
[kW] 3.75 5.5 7.5 11 15 18.5 27.5
Maximum servo amplifier capacity [kW] 3.5 5 7 11 15 15 22
Total of connectable servo
motor rated currents
[A] 33 46 61 90 115 145 215
Short-time rating
Total capacity of applicable servo motors, 300% torque, 60 s
(Note 1)
Output
Regenerative
braking torque
Continuous rating 100% torque
Rated input AC voltage/frequency 3-phase 200 V AC to 220 V AC 50 Hz, 200 V AC to 230 V AC 60 Hz
Permissible AC voltage fluctuation 3-phase 170 V AC to 242 V AC 50 Hz, 170 V AC to 253 V AC 60 Hz
Permissible frequency fluctuation ± 5%
Power supply
Power supply capacity
(Note 2)
[kVA] 17 20 28 41 52 66 100
IP rating (JEM 1030), cooling method Open type (IP00), forced cooling
Ambient temperature -10 °C to 50 °C (non-freezing)
Ambient humidity 90% RH or less (non-condensing)
Environment
Ambience
Indoors (no direct sunlight), free from corrosive gas, flammable gas,
oil mist, dust, and dirt
Altitude, vibration 1000 m or less above sea level, 5.9 m/s
2
or less
Molded case circuit breaker or leakage
current breaker
30AF
30A
50AF
50A
100AF
75A
100AF
100A
225AF
125A
225AF
125A
225AF
175A
Magnetic contactor S-N20 S-N35 S-N50 S-N65 S-N95 S-N95 S-N125
Note 1. This is the time when the protective function of the FR-CV is activated. The protective function of the servo amplifier is
activated in the time indicated in section 10.1.
2. When connecting the capacity of connectable servo amplifier, specify the value of servo amplifier.