FTS 370d/w/r Revision 10 – 1/09/2015 73
Event Log
The Event Log displays all events or
alarms (up to 500) affecting the operation
of the SC 370. A few examples of events
that may be found in the event log are:
MODE OVR (Mode Override)
BCN1 COMM (Beacon1
Communication failure)
MKRT1 COMM (Marker Tier 1
Communication failure)
REBOOT EVENT (System Reboot)
All events, except “REBOOT EVENT”
and Mode Override, are followed by an
arrow and either “ALM” (Alarm) or
“RST” (Restore) to show their current
state. Mode Override is indicated as either
“On” of “Off”. The Age of the event is
shown in days – hours – minutes format
since the event occurred.
Note: The SC 370 maintains event
times since the last “REBOOT EVENT”.
Events only (cumulative up to 500) are
maintained prior to the “REBOOT
EVENT”.
Configuration
The Configuration menu provides access
to program all functions of the lighting
system except “Control Type” (System 1 –
System 6) which must be programmed
through the user interface of each
connected SC 370. A pictorial of the top
level Configuration menu follows this text.
The headings following the pictorial
provide a brief overview of each top level
Configuration menu option.
Tower Lighting
The Tower Lighting menu provides all
programming options discussed in Section
3 “Site Tower Config”. It also adds the
option to input the site name and site ID.
Komentarze do niniejszej Instrukcji