Auxiliary Interface Registers
Address Read/Write Register Name Description / Values
300 R/W Auxiliary Interface Control Type 0: Disabled, 1: Modbus, 2: DC Input
301 R/W Command Lights On/Off 0: Lights on, 1: Lights off
302 R Lights-On Confirmation
1: Pending (Command has been sent to Beacon)
2: ON Success (Beacon has confirmed a Lights On
command)
3: OFF Success (Beacon has confirmed a Lights Off
command)
4: Failed (Command has not be confirmed within 10
seconds)
303 R/W ‘Heartbeat’ Configuration
(1 – 99): not valid inputs – 100 (10.0s) minimum time
required.
100 - 65535: the time in multiples of 100 milliseconds to
default lights on if not ‘kicked’
304 W ‘Heartbeat’
Write value of 0x55AA. If register is not written to within
the time configured in Register 303, then lights will be
turned on until commanded to be off again
305 R/W
Confirmation Relay Output
Configuration
1: MODE relay output
2: COMM ALARM relay output
3: GPS SYNC ALARM relay output
4: PHOTODIODE ALARM relay output
5: MARKER ALARM relay output
6: NIGHT ALARM relay output
7: DAY ALARM relay output
306 R Last Beacon Status
0: Lights on, 1: Lights off
Bit 1) Beacon 2 - 0: Lights on, 1: Lights off
Bit 2) Beacon 3 - 0: Lights on, 1: Lights off
Bit 3) Beacon 4 - 0: Lights on, 1: Lights off
Bit 4) Beacon 5 - 0: Lights on, 1: Lights off
Bit 5) Beacon 6 - 0: Lights on, 1: Lights off
307 R Last Marker Status
0: Lights on, 1: Lights off
Bit 1) Marker Tier 2 - 0: Lights on, 1: Lights off
Bit 2) Marker Tier 3 - 0: Lights on, 1: Lights off
Bit 3) Marker Tier 4 - 0: Lights on, 1: Lights off
Bit 4) Marker Tier 5 - 0: Lights on, 1: Lights off
Bit 5) Marker Tier 6 - 0: Lights on, 1: Lights off