FTS 370d/w/r Revision 10 – 1/09/2015 99
QLI Test
and Results Registers
(Continued)
Register
Address Read/Write Register Name Description / Values
32 R System 1 Results
Bit 0
Beacon 1 not tested (0), was tested in White Day (1)
Bit 1 – Beacon 1 passed pretest (0), failed pretest (1)
Bit 2 – Beacon 1 passed inhibit (0), failed inhibit (1)
Bit 3 – Beacon 1 passed restore (0), failed restore (1)
Bit 4 – Beacon 1 not tested (0), was tested in White Night
(1)
Bit 5 – Beacon 1 passed pretest (0), failed pretest (1)
Bit 6 – Beacon 1 passed inhibit (0), failed inhibit (1)
Bit 7 – Beacon 1 passed restore (0), failed restore (1)
Bit 8 – Beacon 1 not tested (0), was tested in Red Night (1)
Bit 9 – Beacon 1 passed pretest (0), failed pretest (1)
Bit 10 – Beacon 1 passed inhibit (0), failed inhibit (1)
Bit 11 – Beacon 1 passed restore (0), failed restore (1)
Bit 12 – Marker 1 not tested (0), was tested in Red Night(1)
Bit 13 – Marker 1 passed pretest (0), failed pretest (1)
Bit 14 – Marker 1 passed inhibit (0), failed inhibit (1)
Bit 15 – Marker 1 passed restore(0), failed restore (1)
33 R System 2 Results See description for Register 32
34 R System 3 Results See description for Register 32
35 R System 4 Results See description for Register 32
36 R System 5 Results See description for Register 32
37 R
System 6 Results
See description for Register 32
38 R
System 1 Expanded Results
Bit 0
Beacon 1 not tested (0), was tested for IR Alarm (1)
Bit 1 – Beacon 1 passed pretest (0), failed pretest (1)
Bit 2 – Beacon 1 passed inhibit (0), failed inhibit (1)
Bit 3 – Beacon 1 passed restore (0), failed restore (1)
39 R
System 2 Expanded Results
See description for Register 38
40 R
System 3 Expanded Results
See description for Register 38
41 R
System 4 Expanded Results
See description for Register 38
42 R
System 5 Expanded Results
See description for Register 38
43 R
System 6 Expanded Results
See description for Register 38
Tower Override
Register
Address Read/Write Register Name Description / Values
60 R/W Mode Override Control
Read: Override Mode Off (0),
White Day (1), White Night
(2), Red Night (3)
Write: White Day (1), White Night (2), Red Night (3),
Cancel Override Mode (4)
NOTE: A write to the Override Time register is required
while writing the Override Control Register. If
commanding a cancel override, the override time register
is irrelevant however.
61 R/W Mode Override Time 0-65535, Override Time in Minutes.