FTS 370d/w/r Revision 10 – 1/09/2015 63
Monitoring
(System 1
Only)
Load Factory Default
Yes /No
Yes Confirm?
Default of Primary / Alternate Monitoring
Local Ethernet
Configuration
IP Address Mode
Static
Dynamic
IP Address XXX.XXX.XXX.XXX
Subnet Mask XXX.XXX.XXX.XXX
Default Gateway XXX.XXX.XXX.XXX
MAC Address XXXXXXXXXXXX
Primary
Data
Monitoring
Monitoring Method: Disabled
Monitoring
Method:
Cellular
Eagle 2.0
Autoupdate: XX Hours -
XX Minutes
Hours (Enter Value Ranging From 0 - 24)
Minutes (Enter Value Ranging From 0 - 59)
Primary Server IP Address (Enter IP Address)
Primary Server Port 54630
Alternate Server IP Address (Enter IP Address)
Alternate Server Port 54630
Listen Port 54631
Sim Card: (AT&T Direct or
AT&T ROW)
1
Select AT&T Direct (SIM is Blue/White
Front, Orange Back)
Select AT&T ROW (Rest Of World) (SIM
Is Solid White)
Monitoring
Method:
RS 485
Modbus
RTU
Autoupdate: Disabled
Baud Rat: 9600
Station Address: 2
Monitoring
Method:
Ethernet
SNMP
2
Autoupdate: XX Hours -
XX Minutes
Hours (Enter Value Ranging From 0 - 24)
Minutes (Enter Value Ranging From 0 - 59)
Primary Server IP Address (Enter IP Address)
Primary Server Port (Enter Port Number Range Is 0 - 65535)
Alternate Server IP Address (Enter IP Address)
Alternate Server Port (Enter Port Number Range Is 0 - 65535)
Listen Port (Enter Port Number Range Is 0 - 65535)
Monitoring
Method:
Ethernet
Modbus
Autoupdate: Disabled
Listen Port: 00502
Station Address: 2
Monitoring
Method:
Ethernet
Eagle 2.0
Autoupdate: XX Hours -
XX Minutes
Hours (Enter Value Ranging From 0 - 24)
Minutes (Enter Value Ranging From 0 - 59)
Primary Server IP Address (Enter IP Address)
Primary Server Port (Enter Port Number Range Is 0 - 65535)
Alternate Server IP Address (Enter IP Address)
Alternate Server Port (Enter Port Number Range Is 0 - 65535)
Listen Port (Enter Port Number Range Is 0 - 65535)
Alternate
Data
Monitoring
Same Menu as Primary Data Monitoring.
3
Commit
Settings
Yes /No
Yes Confirm?
1. Menu option applies to AT&T HSPA modems only. Menu is not shown when Verizon CDMA modem is installed.
2. Ethernet SNMP, if used, must be selected as the Primary Data Monitoring method.
3. Monitoring Options are mutually exclusive. Example: If RS 485 Modbus RTU is selected in either menu, it is removed
from the available options in the other menu.