7.3.2 Software Addressing the IQ-400 Panel (Panels 112-200) Direct Connect
If a user set up includes more than 111 panels, it is necessary to address the panel through the
LiNC-NET software as opposed to the Dipswitch on the panel itself. Every panel from 112 – 200
is manually set to 112, and then given a software address via LiNC-NET.
1. Set SW1 to address 112 on the IQ-400 panel and press
the S1 button. The Dipswitch setting is: 5, 6, 7 = ON and
1, 2, 3, 4, 8 =OFF.
2. Open the ConFigUL program and define the following:
1 Connection Type (Direct Connect or LAN)
2 COM port
3 Baud rate
3. Select the OPEN port button = Open Port OK
4. Enter Panel #1 into the “current panel number” field.
5. Select the “Inquire” button = OK
6. Select the “Logon” button = OK
7. Enter the desired panel address from 112 – 200 in “New Panel number” window.
8. Select the “change number” button = OK
9. Select the “Who’s there” button. The Inquire field will scan for the new panel address.
(Who’s There=200)
10. Select the “Logoff” button = OK then select “Close Port” and exit.
11. Start LiNC-NET and “add” the new panel ID number to your database.
NOTE Switch #8 is used to determine if the IQ-400 communicates via either direct
connect or dial-up communications. Switch #8 is only used to determine if the
connection is Direct Connect or AutoDial.
The ON/OFF designation is in reference to the labels printed on the IQ-400
PCB. Not the switch itself!