Sharp JX-9400 Informacje Techniczne Strona 64

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 211
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 63
assumes that the tracer gas behaves the same as the air: no adsorption and
same buoyancy, which is the case if the tracer concentration is small. It can
be readily understood that if the air is marked at the in let by a short pulse of
tracer gas, and if the tracer molecules follow the air molecules, they will
arrive at a given location at the same time as the air molecules. The time
spent between injection and the detection of most tracer gas molecules by the
analyser is the age of the tracer, hence the age of the air at the air sampling
location. The pulse technique is, however, not the only one and the following
three strategies can be used:
.
Step-down a uniform concentration of trac er is achieved at the beginning
of the test, when the injection is stopped;
.
Step-up the tracer is injected at the air inlet at a constan t rate from the
starting time throughout the test;
.
Pulse a shor t pulse of tracer is released in the air inlet at the starting
time.
The probability functions and the local mean ages at any point, r, can be
calculated from the time history of the net tracer concentration, C
r
(t), which
is the measured concentration minus the background concentration. It was
shown, however, that for rooms with a sing le air inlet and a single air outlet,
the step-up method should be preferred, since it is the easiest to perform and
gives the best accuracy (Roulet and Cretton, 1992).
For the step-up technique, the tracer gas is injected at a constant rate into
the supply air in the outside air duct, starting at a known time t
0
. It should
be ensured that the tracer and the air are fully mixed in the supply duct to
produce a steady concentration, C
3
, at the air inlet. If C
3
cannot be meas-
ured, the equilibrium concentration within the enclosure, C
4
, may be used
instead. The notations for air sampling refer to Figure 2.5.
Tracer gas concentration at the locations where the age of air is looked for
is recorded. The sampling time interval should be short enough to record the
transient evolution of the concentration. It should then be much shorter than
the expected age of air. A good value is one tenth of the nominal time
constant, which can be estimated by dividing the ventilated volume by the
design airflow rate, or better, by the actual airflow rate if it is known.
One important location is in the exhaust duct, where C
e
¼ C
6
is meas-
ured. Recording the evolution of the tracer gas concentration at this location
provides both the actual nominal time constan t and the mean age of air in the
ventilated space. Injection rate is maintained constant until a steady state is
obtained. Depending on the air change efficiency, this may take up to four
time constants. An example of such a record is given in Figure 3.4.
When the concentration stabilizes at a value noted, C
1
, the step-up
experiment is ended. However, it is recommended to continue recording the
concentration after having stopped the tracer gas injection, since this will
provide a second measurement of the age of the air, using the decay method.
For this purpose, the time when injection is closed should be noted, since
this time is the starting time of the decay experiment.
Age of Air and Ventilation Efficiency 43
Przeglądanie stron 63
1 2 ... 59 60 61 62 63 64 65 66 67 68 69 ... 210 211

Komentarze do niniejszej Instrukcji

Brak uwag