Airflow Rates
in Air Handling Units
Air handling units are designed to supply new air to the ventilated zone and to
extract vitiated air from this zone. Many other airflows may be found in such
units, as shown in Figure 2.1.
Measurements of airflow rates in ventilation systems are useful in order to
check if the air follows the expected paths and thus detect potential probl ems
early so they can be corrected, also allowing the optimization of the perfor-
mance of the airflow system. Checks include examining if actual airflow rates
are close to the desired values and if leakages and short-circuits are negligible.
The checks should be performed:
.
when commissioning a new ventilation system in order to ensure that the
system is built according to the design specifications;
.
if there are indoor air quality problems to help finding their causes;
.
before refurbishing a ventilation system in order to accurately identify the
potential problems to be cured by the refurbishment.
Commissioning mechanical ventilation systems is paramount in order to ensure
that they function as designed. This includes not only the measurement of the
main airflow rates and pressure distributions, but also checks that there are no
excessive leakages or shortcuts. It should be noted that commissioning
protocols are available for most units mentioned in the Introduction that func-
tion as designed, while they are not available for units in which airflow rates are
not those designed or for units showing significant leakages or shortcuts.
This chapter proposes methods for measuring most airflow ra tes that occur
in ventilation systems.
Measurement of the airflow rate in a duct
Summary of measurement methods
Common methods used to measure airflow rates in ducts exploit well-known
relationships between flow rate and pressure drop across a restricted section