SERVICE MANUAL
AEXM30GR
S9619AEXM30GR
MULITI SPLIT TYPE
ROOM AIR CONDITIONERS
OUTDOOR UNIT
AE-XM30GR
MODEL
Parts marked with " " are important for maintaining the safety of the set. Be sure to replace these parts with specified ones for maintaining the
safety and performance of the set.
This document has been published to be used for
after sales service only.
The contents are subject to change without notice.
CHAPTER 1. SPECIFICATION
[1] SPECIFICATION ...........................................1-1
[2] EXTERNAL DIMENSION ..............................1-2
[3] CAPACITY TABLE.........................................1-2
[4] ELECTRICAL PARTS....................................1-4
[5] WIRING DIAGRAMS .....................................1-4
CHAPTER 2. EXPLANATION OF CIRCUIT AND OP-
ERATION
[1] BLOCK DIAGARM.........................................2-1
[2] FUNCTIONS..................................................2-2
CHAPTER 3. FUNCTION AND OPERATION OF PRO-
TECTIVE PROCEDURES
[1] PROTECTIVE FUNCTIONS AND OPERA-
TIONS............................................................3-1
[2] TROUBLESHOOTING GUIDE ......................3-2
CHAPTER 4. REFRIGERATION CYCLE
[1] REFRIGERATION SYCLE ............................. 4-1
[2] REFRIGERANT PIPE INSTALLATION
WORKS.......................................................... 4-3
CHAPTER 5. DISASSEMBLING PROCEDURE
[1] OUTDOOR UNIT ........................................... 5-1
Parts Guide
TopPage
CONTENTS
In the interests of user-safety (Required by safety regulations in some countries)
the set should be restored to its original condition and only parts identical to those
specified should be used.
Przeglądanie stron 0
1 2 3 4 5 6 ... 41 42

Podsumowanie treści

Strona 1 - AE-XM30GR

SERVICE MANUALAEXM30GRS9619AEXM30GRMULITI SPLIT TYPEROOM AIR CONDITIONERSOUTDOOR UNITAE-XM30GRMODELParts marked with " " are important fo

Strona 2 - CHAPTER 1. SPECIFICATION

AE-XM30GR2 – 2[2] FUNCTIONS1. FREQUENCY CONTROL1) AC current peak control2) Prevention control of outdoor heat exchanger overheatingIf the temperature

Strona 3 - [3] CAPACITY TABLE

AE-XM30GR2 – 39. PUMP DOWN SWITCHWhen the PUMP DOWN SWITCH (SW1) is pressed for 5 seconds ormore, the total A/C system will start its TEST RUN automat

Strona 4

3 – 1CHAPTER 3. FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES[1] PROTECTIVE FUNCTIONS AND OPERATIONSNO. FunctionOperationDescription Detection time

Strona 5 - [5] WIRING DIAGRAMS

3 – 2[2] TROUBLESHOOTING GUIDE1. SELF-DIAGNOS IS FUNCTION AND DIS PLAY MODE1) To call out the content of the self-diagnosis memory, hold down the emer

Strona 6

3 – 300-011-055-066-0773-088-011 11-022-00-10-20-3-1-2-30-50-4-1-2-5-4-1-2-3Status ofindoor/outdoorunitsIndication byLED1 onoutdoor unit*2Indication o

Strona 7

3 – 413 13-0-114 14-017 17-0-118 18-01919-020 20-03030-0-1Status ofindoor/outdoorunitsIndication byLED1 onoutdoor unit*2Indication on indoor unitConte

Strona 8 - (CONTROL PWB)

3 – 5CAUTION: when attaching or removing the boardWhen operating only the outdoor unit (cooling 55 Hz fixed mode) To make only the outdoor unit run in

Strona 9 - [1] BLOCK DIAGARM

3 – 62. How to distinguish the defective parts1. When all rooms are not cooledOutdoor temp. thermistor TH3 CN8A Green No. 5 to 6Suction thermistor TH4

Strona 10 - [2] FUNCTIONS

3 – 7YesNoYesYesYesYesNoNoNoNoYesNoNoNoNoNoNoNoNoNoYesYesYesYesYesYesYesYesOpen circuit of theoutdoor thermistorReplace thethermistor.Replace the fan

Strona 11 - 11. DEFROST OPERATION

3 – 82. When one room is not cooled (other rooms are cooled)YesYesNoYesNoNoNoYesNoNoYesYesShort circuit of the thermistor errorOpen circuit of the the

Strona 12

AE-XM30GR1 – 1AE-XM30GRService Manual CHAPTER 1. SPECIFICATION[1] SPECIFICATIONNOTE: The condition of star “✩“marked item are ‘ISO5151’: *: Representa

Strona 13 - [2] TROUBLESHOOTING GUIDE

3 – 93. When all rooms are not heatedDoes the air get cooler in thecooling operation mode?Check the four-way valve.Has the cycle been switched?Is AC23

Strona 14 - (3)Correct refrigerant clogs

AE-XM30GR4 – 1AE-XM30GRService Manual CHAPTER 4. REFRIGERATION CYCLE[1] REFRIGERATION SYCLE1. [7 / 9/ 12] class indoor unit is connected UNITA2. [18]

Strona 15 - Outdoor unit in

AE-XM30GR4 – 23. Cycle temperature and pressure in stop valve (AE-XM30GR)Standard conditions (AE-XM30GR)Running unit no operation mode Cool (MAX)

Strona 16 - Resistance

AE-XM30GR4 – 34. PERFORMANCE CURVESNOTE: Total cooling capacity and total input with 4 units running.At Cooling for AY-XPM9FR (for AE-XM30GR)At Heatin

Strona 17 - Resistance (k )

AE-XM30GR4 – 48) Fully open the stop valve (gas side) with hexagon socket screwkey. Turn all the way up to contact.9) Disconnect the gauge manifold ho

Strona 18

AE-XM30GR5 – 1AE-XM30GRService Manual CHAPTER 5. DISASSEMBLING PROCEDURE[1] OUTDOOR UNIT1. PROCEDURE1. Remove the 5 screws fixing the front panel R an

Strona 19 - Replace the indoor

AE-XM30GR5 – 27. Cut the insulators.8. Remove the 2 screws fixing the control box cover.CAUTION: Discharge electrolytic capacitor before touching this

Strona 20

AE-XM30GR5 – 315..Remove the 3 screws fixing the bulkhead.16.Remove the 3 screws fixing the active coil.17.Remove the 1 nut fixing the propeller fan.1

Strona 21 - REFRIGERATION CYCLE

AE-XM30GR5 – 420.Remove the 4 screws fixing the fan motor.2. Position of the thermistorsNOTE: Caution to the position when reinstalling.GreenOrangeBla

Strona 22

AE-XM30GR5 – 53. How to disassemble the control box assembly1. Remove the 4 screws fixing the PWB.2. Unlock the spacer's lock.The position of set

Strona 23

AE-XM30GR1 – 2[2] EXTERNAL DIMENSION[3] CAPACITY TABLERecommended CombinationOutdoor UnitsIndoor UnitsAY-XPM7/9/12FR,GS-XPM9/12/18FGR,GS-XPM7/9/12FRAE

Strona 24

AE-XM30GR5 – 64. Mounting position of thermistors and expansion valvesMounting position of thermistors and expansion valves are shown below. Thermisto

Strona 25 - DISASSEMBLING PROCEDURE

PARTS GUIDEThis document has been published to be usedfor after sales service only.The contents are subject to change without notice.AE-XM30GRMULITI

Strona 26

AE-XM30GR 2[1] OUTDOOR UNIT PARTS 14-32-52-42-24-74-42-32-84-32-91-5-21-5-14-82-71-14-92-52-11-21-41-41-34-154-162-64-12-171-112-361-601-361-631-521-6

Strona 27

AE-XM30GR3NO. PARTS CODEPRICE RANKNEW MARKPART RANKDESCRIPTION[1] OUTDOOR UNIT PARTS 11-1 CMOTLB051JBEZ BX Fan motor1-2 LANG-A540JBWZ AU Terminal boar

Strona 28

AE-XM30GR4[2] OUTDOOR UNIT PARTS 23-173-143-353-253-353-101-542-353-233-133-113-222-671-791-692-333-211-783-182-682-693-124-63-73-93-82-662-302-633-30

Strona 29

AE-XM30GR5NO. PARTS CODEPRICE RANKNEW MARKPART RANKDESCRIPTION[2] OUTDOOR UNIT PARTS 21-54 QW-IZA100JBZZ AZ Compressor cord1-69 RH-HXA032JBZZ AX Therm

Strona 30

AE-XM30GR6NO. PARTS CODEPRICE RANKNEW MARKPART RANKDESCRIPTION[4] PACKING PARTSNO. PARTS CODEPRICE RANKNEW MARKPART RANKDESCRIPTION1-30 RRLYDA012JBZZ

Strona 31

AE-XM30GR7INDEXPARTS CODE No.PRICE RANKNEW MARKPART RANK[ C ]CCHS-A856JBKZ 1-2-14 BKCCIL-A112JBEZ 2-3-8 AXCMOTLB051JBEZ 1-1-1 BXCPADBA072JBKZ 4-5-1 A

Strona 32 - [1] OUTDOOR UNIT PARTS 1

AE-XM30GR8QW-VZE605JBZZ 3-1-55 AKQW-VZE624JBZZ 3-1-25 APQW-VZE625JBZZ 3-1-26 APQW-VZF079JBZZ 3-1-8 AUQW-VZF080JBZZ 3-1-20 AUQW-VZF081JBZZ 3-1-22 AUQW-

Strona 34 - [2] OUTDOOR UNIT PARTS 2

AE-XM30GR1 – 3COOLING CAPACITY TABLEHEATING CAPACITY TABLEOperating StatusCombination of Indoor UnitsCooling Capacity (kW) Running Current (A)Power Co

Strona 35

EndPageCOPYRIGHT © 2006 BY SHARP CORPORATIONALL RIGHTS RESERVED.No part of this publication may be reproduced, storedin retrieval systems, or transmi

Strona 36 - [4] PACKING PARTS

P1 / 1General The service parts of the coil for expansion valve is changed.Model No.GU-XR18ER , GU-XR24ER , GU-XR27ER , GU-XR18FR , GU-XR24FR , GU-XR2

Strona 37

GeneralActive filter has been changed as follows.ModelModel name DestinationEffective fromAE-XM30GR EuropeReasonStandardizationInterchangeabilityJun-0

Strona 38

AE-XM30GR1 – 4[4] ELECTRICAL PARTS[5] WIRING DIAGRAMS2-Room18 12 OFF - 4.86 3.24 OFF - 8.1 (3.6-9.0j 11.2 (3.8-15.1) 2450 (830-3300)18 9 OFF - 5.40 2.

Strona 39

AE-XM30GR1 – 5CONTROL P.W.B and DISPLAY P.W.Bfrom 4 WAY VALVEfrom CONTROL BOXfrom DIODE BRIDGEDB1 "~"from HEAT-SINKTHERMISTORfrom THERMISTOR

Strona 40

AE-XM30GR1 – 6IPM P.W.B.from CONTROL PWB BCN1from CONTROL PWBBCN2from CONTROL PWBCN14from ELECTROLTIC CAPACITOR C10 "+"from ELECTROLTICCAPAC

Strona 41 - Technical Repor

AE-XM30GR1 – 7(CONTROL PWB)TU2FC7FC3FC8GREEN/YELLOWBLUEPURPLEREDORANGEBROWNBROWNBROWNBROWN21FC2FC4FC6FC5YELLOWYELLOWYELLOWWHITEWHITEIoP-+L1 L2SACT3242

Strona 42 - Technical Re

AE-XM30GR2 – 1AE-XM30GRService Manual CHAPTER 2. EXPLANATION OF CIRCUIT AND OPERATION[1] BLOCK DIAGARMCPUPump down switch circuitUnit A thermo. circui