I/O Modules 135
Design of the Process Data for PROFIBUS-DP
WAGO-I/O-SYSTEM 750
Bus System
5.2 Design of the Process Data for PROFIBUS-DP
Depending on how the coupler is parameterized, the status bytes (S), control
bytes (C) and data bytes (D0...Dn) of the byte or word orientated modules are
transmitted via PROFIBUS in Motorola or Intel format.
Attention
For the meaning of input and output bits or bytes of the individual I/O
module please refer to the corresponding I/O module description.
5.2.1 2 DI I/O Modules
750-400, 750-401, 750-405, 750-406, 750-407, 750-410, 750-411,
750-412, 750-413, 750-416, 750-427, 750-435, 750-438
Process Image Length in [Bit]
Diagnostics information in the
PROFIBUS process image
Input Output
Yes (not possible) - -
No 2 0
5.2.2 2 DI I/O Modules with Diagnostics
750-419, 750-425 (1 bit diagnostics / channel)
Process Image Length in [Bit]
Diagnostics information in the
PROFIBUS process image
Input Output
Yes 4 0
No 2 0
750-418 (1 bit diagnostics / channel, 1 bit confirmation / channel)
Process Image Length in [Bit]
Diagnostics information in the
PROFIBUS process image
Input Output
Yes 4 2
No 2 2