Commissioning CarboVis 70x IQ TS
3 - 8
ba75950e02 11/2012
3.4.2 Sensor structure
The physical sensor is the sensor with the instrument or model desig-
nation, CarboVis 70x IQ TS. The physical sensor processes the mea-
surement signal (absorbance spectrum) and supplies up to 5
measurement results to the IQ S
ENSOR NET. The measurement results
are administrated like 5 sensors that differ in hierarchy as follows:
Main sensor The sensor for carbon measurement is the main sensor.
It registers on the system under the designation, CarboVis 70x IQ TS
and the series number of the physical sensor.
Secondary sensor The sensor for the measurement of total suspended solids is the
secondary sensor.
It registers on the system under the designation, SolidVis 70x IQ and
the series number of the physical sensor.
Virtual sensors All other sensors for carbon measurement are virtual sensors.
You register on the system under the designation, CarboVis 70x IQ TS
and the series number of the physical sensor.
Sensor overlapping
settings and functions
Some settings and functions are sensor overlapping. Sensor overlap-
ping settings are generally edited in the setting menu of the main sen-
sor.
These are the most important sensor overlapping settings and func-
tions:
Measuring location
Times of the measuring cycle (
Meas. interval
,
Cleaning duration
,
Adjustment phase
etc.)
Signal smoothing
Details on sensor overlapping functions are given in the following
section.