Running Diagnostics
4-22 72A-1230 Rev. F
July 22, 2005
The first six of these tests are applicable to the M4100; the last one is not. Use
of the Communications Loopback Test is described in ”Communications
Loopback Test” on page 4-40.
Follow these recommendations in deciding when to run each test:
* When contacting Doble by telephone or e-mail
two tests, including the contents of the Calver.log file, located in the DTA
directory.
Diagnostic Test Run the test when suggested by a
displayed message, when indicated in a
troubleshooting flow chart or table, or:
System Status * Run this test if you are experiencing any
malfunction or error.
Calibration Verification* 1. Run this test periodically to run a mock
specimen measurement, which checks
all system connections, including high
and low voltage cables.
2. Run this test after replacing a
component or otherwise repairing the
M4100.
Field Recalibration Run to calibrate the test set when one of the
calibration verification tests results in a Fail
or Re-cal rating.
Subsystem Diagnostics Run this test to exercise specific M4100
components.
M4100 Component List Run this test to obtain a list of recognized
M4100 components and their revision
numbers.
Thermal Profile Run this test if the M4100 appears to be
overheating or if an over-temperature
indication appears.
Communication Loopback
Test
Run to check communications between the
M4200c Controller (or laptop) and the
M4100 Instrument.